Laserfiche WebLink
9. Note that the sanitary sewer line servicing the properly is likely to come in conflict with <br />any building expansion. It is suggested that this be rerouted to avoid that occurrence, <br />should expansion be desired in the future. <br />Response: The sewer lateral alignment has been revised to allow possible future <br />building expansion without potential conflicts. <br />70. On Sheet C2, 1 note 70 posts set into the sidewalk along the front of the building. What <br />is the purpose for these? The plans suggest a curb along the front of the building. The <br />same situation exists on the south side of the building, with no posts. <br />Response: The posts you mention are bollards that Autozone typically places <br />along the front of the building. particularly where there are windows. This <br />provides an additional element of safety. <br />11. On Sheet A2, show the location of the mechanical units. They must be screened from <br />the public streets. <br />Response: The mechanical units are roof mounted and screened from view from <br />the public street. Please refer to Sheet A2, Note 19. <br />Enclosed are two full sized and one 11 "x17" copies of the revised plans. Please do not hesitate <br />to call me if you have any questions or need additional information. <br />Sincerely, <br />CEI Engineering Associates, Inc. <br />afael A. B~ssi, PE <br />roject Manager <br />nc. Resubmttal package <br /> <br />=~ <br />