nited <br />ervices <br />roup~' <br />2i22ios <br />Notes: A faceshield with a minimum arc rating of 8, with wrap-around guarding to <br />protect not only the face, but also the forehead, ears, and neck (or, alternatively, a flash <br />suit hood), is required. <br />Note6: Alternate is to use two sets of FR coveralls (the inner with a minimum arc rating <br />of 4 and outer coverall with a minimum arc rating of 5) over non-melting or untreated <br />natural fiber clothing, instead of FR coveralls over FR shirt and FR pants over non- <br />melting or untreated natural fiber clothing. <br />Note7: If voltage-rated gloves are required, the leather protectors worn external to the <br />rubber gloves satisfy this requirement. <br />3 of 3 <br />