Laserfiche WebLink
City of Elk River Design Standards <br />When watermain is constructed, separated from the active sy-stem, the Contractor shall still be <br />required to chlorinate, pressure test, and flush the new work in accordance with the <br />specifications. This may require additional work operation to fill and flush the system. <br />The Contractor shall furnish the pump, pipe connections, gauges, and measuring equipment, and <br />shall perform the testing in the presence of ERMU. The pressure gauge for the test shall be an <br />Ashcroft Model 1082 with 4 1/2-inch dial face at 1 psi increments or approved equal. Where <br />permanent air vents are not provided, the Contractor shall pro�ride and install corporation cocks <br />at the high points as needed for release of air as the line is filled with water. <br />Any defective joints, pipe, fittings, valves, or hydrants revealed during the testing or before final <br />acceptance of the work shall be satisfactorily corrected and the tests shall be repeated until the <br />specified requirements have been met. <br />A. Pressure Test: The section being tested shall be slowly� filled with water and the specified <br />test pressure shall be applied after all air has been expelled from the pipe. A hydrostatic <br />pressure of 150 pounds per square inch, gauge pressure, measured at the lowest point of <br />elevation, shall be applied by means of a pump connected to the pipe in a satisfactory <br />manner. <br />The gauge pressure shall be checked after a minimum of two hours. A pressure drop of <br />1 psi or less over a 2 hour period shall be considered acceptance for the test section. If <br />the pressure drop is greater than 1 psi the Contractor shall investigate the cause and take <br />corrective action. The Contractor must make e�-ery effort to expel all air in the test <br />section which may- be causing a test failure. This may� require the Contractor to tap a <br />corporation at a high point of the main on the top of the pipe to release trapped air. <br />Service pipe shall tvpicallv be tested in conjunction with the main line testing. However, <br />services may� be tested separately- at 100 psi, with the corporation stops open. <br />The Contractor ma�- ha�re to perform additional pressure testing if during the flushing <br />operation there is evidence of debris being flushed out of the system. This may be due <br />to poor construc�ion practices and result in valves not closing tight after having done the <br />original pressure test. Retesting shall be at the discretion of the Water Superintendent. <br />2. Disinfection of Watermains <br />Before being placed in service, the completed watermain installation shall be disinfected and <br />flushed, and after the final flushing the water shall be tested for bacteriologic qualin� and found <br />to meet the standards prescribed by the Minnesota Department of Health. The disinfection <br />materials and procedures and the collection and testing of water samples shall at a minimum be <br />in accordance with the provisions of A�X��X�A C651, Disinfecting Watermains, and as well as <br />meet the requirements of the Minnesota Department of Health. <br />Where an existing watermain is cut for the installation of a hydrant, for lowering the watermain, <br />or for reasons determined by the Engineer, the pipe and fittings proposed to be installed shall be <br />disinfected prior to installation as follows: <br />(1) The interior of the pipe and fittings shall be cleaned of all dirt and foreign material. <br />(2) The interior of the pipe and fittings shall be thoroughly swabbed or sprayed with a 1 <br />percent minimum hy-pochlorite solution. <br />OO City of Elk River, Minnesota — All rights reserved I 8 <br />