Laserfiche WebLink
<br />Engineering <br />Guide <br />Specifications <br /> <br />General: The GeoSource heat pump system <br />and the ground loop field shall be one system and <br />include all interconnecting piping and controls to <br />provide an efficient, harmoniously-balanced <br />package. <br /> <br />Ground Loop: The ground loop field shall be <br />constructed of high-density polyethylene or poly- <br />butylene piping. Its layout shall be of parallel <br />circuits terminated at a reducing header of <br />reverse-return design. All underground joints <br />shall be fusion-welded. The ground loop field <br />shall be designed to provide a 250F <br />water/antifreeze mixture to the heat pumps during <br />the month of January. The antifreeze shall be <br />GTF heat transfer fluid mixed 50% by volume <br />with water of 100-PPM grain hardness or less. <br />The heat pumps shall work over extended-range <br />ground-loop temperature variations (150F to <br />11 OOF). The piping shall consist of sufficient <br />pump capacity with suction and discharge <br />pressure ports. Valves shall be incorporated for <br />purging all debris and air from the total system. <br />All backfilling and grouting shall be done in <br />accordance with IGSHP A guidelines. All heat <br />pumps shall be installed with PIT ports for <br />pressure and temperature measurement. <br /> <br />Cabinet: The heat pump cabinet shall be <br />constructed of heavy-gauge Galvaneal corrosion- <br />resistant steel coated with a baked-on powder <br />epoxy finish and shall be insulated with 1/2" <br />high-density fiberglass insulation. It shall be <br />oriented to allow complete component service <br />access from the front. <br /> <br />Legend for Tables <br /> <br />BTU/hr <br />CAP <br />COP <br />CFM <br />DB <br />DHW <br />dP <br />EER <br />EWT <br />FLA <br /> <br />Heating or cooling capacity <br />Capacity <br />Coefficient of performance (BTU/hr out + BTU/hr in) <br />Cubic feet per minute <br />Dry-bulb entering air temperature <br />Domestic hot water <br />Pressure drop across heat pump (in feet of water and psi) <br />Energy efficiency ratio (BTU/hr out + watts in) <br />Entering water temperature (in degrees Fahrenheit) <br />Full-load amperage <br /> <br />Refrigerant Circuit: Compressors shall be <br />hermetically-sealed high-efficiency compliant <br />scroll mounted on vibration isolators. The water <br />heat exchanger shall be either non-coaxial open- <br />center canister-type with enhanced heat <br />exchanger surface, or stainless steel brazed plate. <br />An optional domestic water desuperheater coil of <br />vented double copper construction for potable <br />water shall have an over-temperature control. The <br />expansion device shall be a bi-flow thermostatic <br />metering valve. The reversing valve shall be of <br />copper construction with 24VAC control with <br />fail-to-heating positioning. All heat pumps shall <br />have a factory-installed filter/drier. <br /> <br />Controls: All units shall incorporate both low- <br />and high-pressure switches and freeze protection <br />with total refrigerant lockout and manual reset <br />upon application. All units shall have random <br />start and be anti-short cycle protected. <br /> <br />Testing and Warranty: All heat pumps shall <br />be factory run-tested with ASHRAE test lab <br />standards at simulated design conditions for a <br />minimum of two hours to assure component and <br />system integrity. All units shall be tested by and <br />rated in accordance with IS0-13256 and CSA <br />C22.2 test laboratory safety and performance <br />standards. All heat pumps shall carry a 2/5 <br />residential or a 1/5 commercial warranty. <br /> <br />GPM Gallons per minute of water flow <br />HE Heat extracted <br />HR Heat rejected <br />KW Kilowatt input <br />LRA Locked-rotor amperage <br />MBTU/hr Btulhr X 1000 <br />RLA Rated-load amperage <br />VA Volt-amperes <br />WB Wet. bulb entering air temperature <br /> <br />All Pressure Drop Ratings are for Pure Water <br />Performance values are +/- 10%, and are subject to change without notice. <br />