Laserfiche WebLink
5'-0" <br />EDGE OF MAT OR <br />BACK OF CURB - <br />"HYDRAFINDER" <br />MINIMUM COVER AS REQUIRED IN <br />SPECIFICATIONS OR AS SHOWN <br />ON PLANS. <br />TRACER WIRE <br />VALVE WITH <br />MECHANICAL JOINT <br />TEE AND VALVE BOX <br />MECHANICAL JOINT TEE <br />FOR SIZE FIRE HYDRANT <br />LINE , <br />TRACER WIRE ACCESS BOX <br />AND GROUNDING ROD <br />SAME AS FOR WATER <br />SERVICE SHOWN IN <br />DETAIL 3408 <br />JOINT RESTRAINING COUPLING-TWO <br />3/4" ALL THREAD RODS <br />0.75" - 1.5" <br />DRAIN ROCK <br />CONCRETE <br />BLOCK <br />N OTE: <br />ALL HYDRANT LEADS SHALL BE RESTRAINED FROM THE MAIN TO THE HYDRANT <br />THROUGH THE USE OF THREADED RODS OR MEGALUGS AS RESTRAINTS IN <br />ACCORDANCE WITH THE STANDARD DETAIL PLATES. <br />REV: 2/2017 <br />C' •, <br />HYDRANT RESTRAINT DETAIL <br />STANDARD <br />PLATE <br />N0. <br />3402 <br />