Laserfiche WebLink
SCHEDULE 3 - DISTRIBUTED ENERGY RESOURCES INTERCONNECTION PROCESS <br />proper coordination with other protective devices. For example, the over-current relay <br />monitoring the interconnection breaker shall operate fast enough for a fault on the <br />51V is a voltage restrained or controlled over-current relay and may be required to <br />provide proper coordination with the Area EPS. <br />(b) Over-voltage relays (IEEE Device 59) shall operate to trip the Distributed Generation per the <br />requirements of IEEE 1547. <br />(c) Under-voltage relays (IEEE Device 27) shall operate to trip the Distributed Generation per the <br />requirements of IEEE 1547 <br />(d) Over-frequency relays (IEEE Device 81O) shall operate to trip the Distributed Generation off- <br />line per the requirements of IEEE 1547. <br />(e) Under-frequency relay (IEEE Device 81U) shall operate to trip the Distributed Generation off- <br />line per the requirements of IEEE 1547. For Generation Systems with an aggregate capacity <br />greater then 30kW, the Distribution Generation shall trip off-line when the frequency drops <br />below 57.0-59.8 Hz. typically this is set at 59.5 Hz, with a trip time of 0.16 seconds, but <br />coordination with the Area EPS is required for this setting. <br />The Area EPS will provide the reference frequency of 60 Hz. The Distributed <br />Generation control system must be used to match this reference. The protective <br />relaying in the interconnection system will be expected to maintain the frequency of <br />the output of the Generation. <br />(f) Reverse power relays (IEEE Device 32) (power flowing from the Generation System to the Area <br />EPS) shall operate to trip the Distributed Generation off-line for a power flow to the system <br />with a maximum time delay of 2.0 seconds. <br />(g) Lockout Relay (IEEE Device 86) is a mechanically locking device which is wired into the close <br />circuit of a breaker or switch and when tripped will prevent any close signal from closing that <br />device. This relay requires that a person manually resets the lockout relay before that device <br />can be reclosed. These relays are used to ensure that a denergized system is not reenergized <br />by automatic control action, and prevents a failed control from auto-reclosing an open <br />breaker or switch. <br />(h) Transfer Trip All Generation Systems are required to disconnect from the Area EPS when <br />the Area EPS is disconnected from its source, to avoid unintentional islanding. With larger <br />Generation Systems, which remain in parallel with the Area EPS, a transfer trip system may <br />be required to sense the loss of the Area EPS source. When the Area EPS source is lost, a <br />signal is sent to the Generation System to separate the Generation from the Area EPS. The <br />size of the Generation System vs the capacity and minimum loading on the feeder will <br />dictate the need for transfer trip installation. The Area EPS interconnection study will <br />identify the specific requirements. <br />If multiple Area EPS sources are available or multiple points of sectionalizing on the <br />Area EPS, then more than one transfer trip system may be required. Area EPS <br />interconnection study will identify the specific requirements. For some installations <br />the alternate Area EPS source(s) may not be utilized except in rare occasions. If this <br />is the situation, the Interconnection Customer may elect to have the Generation <br />System locked out when the alternate source(s) are utilized, if agreeable to the Area <br />EPS operator. <br />(i) Parallel limit timing relay (IEEE Device 62PL) set at a maximum of 120 seconds for <br />346 <br />