IllGREAT <br /> RIVER System Operations Outage Tracking - Daily Outage Report <br /> ENERGY- <br /> Wright-Hennepin Cooperative Electric Association <br /> Outage ID: 16858 Reason: 31F,clear,winds NW 10mph.Line tripped&reclosed auto twice,held 25 sec,tripped&reclosed auto twice,then <br /> tripped to lockout.At 1144,At 1216,MOS EMSM4 was opened by SCADA&Elk River 6NB6 was closed.At 1207, <br /> WH crew opened SW BLS1&Maple Lake 1NB1 was closed by SCADA.WH crews reported broken insulator at BL <br /> str#14.Top phase laying on bottom phase insulator.At 1217,WH opened SW H14S1&started backfeeding <br /> Black Lake load.At 1246,MOS EMSM4 was closed.At 1315,all load backfed.All 3 insulators were replaced& <br /> RTN 1753. <br /> Breaker Distance Fault Type <br /> Elk River 56 6NB6-Maple Lake Line PRI 21.28 miles BG <br /> Elk River 56 6NB6-Maple Lake Line SEC 21.03 miles BG <br /> Maple Lake 1NB1-Elk River Line 6.11 miles BG <br /> Line Init.Cause Sus.Cause Start End Duration <br /> 600051 69 Elk River 6NB6-Maple Lake 1NB1(BL,EM,EMX) IF IF 03/16/2019 11:42 03/16/2019 13:15 1 hour 33 <br /> minutes <br /> Substation T/D Consumers Init.Cause Sus.Cause Start End Duration <br /> HXH003 Albertville T 1,840 IF IF 03/16/2019 11:42 03/16/2019 12:07 25 minutes <br /> HXH014 Black Lake T 1,344 IF IF 03/16/2019 11:42 03/16/2019 13:15 1 hour 33 <br /> minutes <br /> Note: Backfed. <br /> OUTG-018-Daily Outage Report - 1- 3/18/19 3:33:41 PM <br /> 189 <br />