Laserfiche WebLink
<br />(7) Each permit holder shall have at least two water-type or equivalent fire <br />extinguishers of not less than 2 1/2-gallon capacity in the area where the <br />fIreworks are sold or stored. <br /> <br />(8) There shall be at least two exits from all buildings where fIreworks are being <br />sold or stored. <br /> <br />(9) In buildings without an approved automatic sprinkler system, fireworks sales <br />displays and/ or storage shall be limited to 50 pounds net pyrotechnic <br />composition or 200 pounds gross weight, if the pyrotechnic composition <br />weight is not known. <br /> <br />(10) In buildings with an approved automatic sprinkler system, fireworks sales <br />displays and/or storage shall be limited to 100 pounds net pyrotechnic <br />composition or 400 pounds gross weight, if the pyrotechnic composition <br />weight is not known. <br /> <br />(11) A list of all fireworks displayed for sale and stored on the property must be <br />posted in a conspicuous location near the display/storage area. The list shall <br />include the name, weight and quantity of the fireworks and shall be <br />accompanied by the material safety data sheets. Upon request, samples of the <br />fireworks shall be made available to the fIre chief or his designee for testing. <br /> <br />(12) A permit granted pursuant to this division is not transferable. <br /> <br />(13) Fireworks fffi:lSt shall not be sold to people tlfttief less than 18 years eM of <br />age. <br /> <br />(Ord. No. 02-08, ~ 1(209.08),5-28-2002) <br />