Laserfiche WebLink
SCHEDULE 3—INTERCONNECTION PROCESS,TECHNICAL REQUIREMENTS,AND OPERATING PROCEDURES <br /> 4. Interconnection Issues and Technical Requirements <br /> A)General Requirements -The following requirements apply to all interconnected generating equipment. The <br /> Area EPS shall be the source side and the customer's system shall be the load side in the following <br /> interconnection requirements. <br /> i)Visible Disconnect-A disconnecting device shall be installed to electrically isolate the Area EPS from the <br /> Generation System.The only exception for the installation of a visible disconnect is if the generation is <br /> interconnected via a mechanically interlocked open transfer switch and installed per the NEC (702.6) <br /> "so as to prevent the inadvertent interconnection of normal and alternate sources of supply in any <br /> operation of the transferequipment." <br /> The visible disconnect shall provide a visible air gap between Interconnection Customer's <br /> Generation and the Area EPS in order to establish the safety isolation required for work on the <br /> Area EPS. This disconnecting device shall be readily accessible 24 hours per day by the Area <br /> EPS field personnel and shall be capable of padlocking by the Area EPS field personnel. The <br /> disconnecting device shall be lockable in the open position. <br /> The visible disconnect shall be a UL approved or National Electrical Manufacture's Association <br /> approved, manual safety disconnect switch of adequate ampere capacity. The visible <br /> disconnect shall not open the neutral when the switch is open. A draw-out type circuit breaker <br /> can be used as a visual open. <br /> The visible disconnect shall be labeled, as required by the Area EPS Operator to inform the <br /> Area EPS field personnel. <br /> ii) Energization of Equipment by Generation System —The Generation System shall not energize a de- <br /> energized Area EPS. The Interconnection Customer shall install the necessary padlocking (lockable) <br /> devices on equipment to prevent the energization of a de-energized electrical power system. Lock out <br /> relays shall automatically block the closing of breakers or transfer switches on to a de-energized Area <br /> EPS. <br /> iii)Power Factor-The power factor of the Generation System and connected load shall be as follows; <br /> (1)Inverter Based interconnections — shall operate at a power factor of no less than 90%.at the <br /> inverterterminals. <br /> (2)Limited Parallel Generation Systems,such as closed transfer or soft-loading transfer systems shall <br /> operate at a power factor of no less than 90%, during the period when the Generation System is <br /> parallel with the Area EPS,as measured at the Point of Common Coupling. <br /> (3)Extended Parallel Generation Systems shall be designed to be capable of operating between 90% <br /> lagging and 95% leading. These Generation Systems shall normally operate near unity power <br /> factor (+/-98%) or as mutually agreed between the Area EPS operator and the Interconnection <br /> Customer. <br /> iv) Grounding Issues <br /> (1)Grounding of sufficient size to handle the maximum available ground fault current shall be <br /> designed and installed to limit step and touch potentials to safe levels as set forth in "IEEE Guide <br /> for Safety in AC Substation Grounding",ANSI/IEEE Standard 80. <br /> (2) It is the responsibility of the Interconnection Customer to provide the required grounding for the <br /> Generation System. Agood standard for this is the IEEE Std. 142-1991 <br /> Interconnection Process for Distributed Generate Systems <br />