Elk River GHG Baseline Inventory Apendix
<br />City of Elk River Buildings and Grounds Detail
<br />City Operations Carbon Baseline
<br />Buildings and Grounds
<br />Facility 2015 Baseline % Total
<br />Electricity Use
<br />Base Accounts (actual)KWH
<br />City Hall / Public Utilities 337,638.33 10.50%
<br />Ice Arena 946,768.82 29.44%
<br />Library 213,751.33 6.65%
<br />Public Safety 778,351.67 24.20%
<br />Fire Station 1 63,539.93 1.98%
<br />Lions Park Center 31,825.26 0.99%
<br />North Bound Liquor 206,956.56 6.44%
<br />Public Works 332,875.00 10.35%
<br />Senior Activity Center 115,358.67 3.59%
<br />Waste Water Treatment Plant*0.00 0.00%
<br />West Bound Liquor 188,840.94 5.87%
<br />Subtotal Base Accounts 3,215,906.52 100.00%
<br />New Accounts (actual)
<br />Subtotal New Accounts 0.00 0.00%
<br />Total Electrical Use (actual)3,215,906.52 100.00%
<br />Natural Gas Use
<br />Base Accounts (actual)Therms
<br />City Hall / Public Utilities 31,421.15 23.20%
<br />Ice Arena 45,906.41 33.89%
<br />Library 0.00 0.00%
<br />Public Safety 13,590.79 10.03%
<br />Fire Station 1 9,274.43 6.85%
<br />Lions Park Center 2,852.06 2.11%
<br />North Bound Liquor 4,200.64 3.10%
<br />Public Works 21,271.12 15.70%
<br />Senior Activity Center 4,486.45 3.31%
<br />Waste Water Treatment Plant 0.00 0.00%
<br />West Bound Liquor 2,443.97 1.80%
<br />Subtotal Base Accounts 135,447.02 100.00%
<br />New Accounts (actual)
<br />Subtotal New Accounts 0.00 0.00%
<br />Total Natural Gas Use (actual)135,447.02 100.00%
<br />Energy Use Intensity (EUI - Site)
<br />Base Accounts (actual)Building Area (sF)Total KBTU EUI
<br />City Hall / Public Utilities 45,195 4,294,137.14 95.01
<br />Ice Arena 62,125 7,821,016.13 125.89
<br />Library 16,818 729,319.55 43.37
<br />Public Safety 35,898 4,014,814.67 111.84
<br />Fire Station 1 14,370 1,144,241.65 79.63
<br />Lions Park Center 8,050 393,793.84 48.92
<br />North Bound Liquor 12,610 1,126,199.73 89.31
<br />Public Works 81,400 3,262,881.23 40.08
<br />Senior Activity Center 10,600 842,249.23 79.46
<br />Waste Water Treatment Plant 9,264 8,231,961.98 888.60
<br />West Bound Liquor 10,388 888,722.26 85.55
<br />Total for Base Accounts 306,718 32,749,337.42 106.77
<br />New Accounts (actual)
<br />Total for New Accounts 0 0.00 0.00
<br />Average EUI (actual)306,718 32,749,337 106.77
<br />GHG Emissions
<br />Electricity Emissions (actual)
<br />Factor (Metric Tonnes per KWH)*0.00078
<br />Base Accounts (Metric Tonnes)2,508.41 100.00%
<br />New Accounts (Metric Tonnes)0.00 0.00%
<br />Subtotal Electric GHG Emissions 2,508.41 Metric Tonnes
<br />Natural Gas Emissions (actual)
<br />Factor (Metric Tonnes per Therm)0.005302
<br />Base Accounts (Metric Tonnes)718.14 100.00%
<br />New Accounts (Metric Tonnes)0.00 0.00%
<br />Subtotal Gas GHG Emissions 718.14 Metric Tonnes
<br />Total GHG Emissions (actual)3,226.55 Metric Tonnes
<br />Total GHG Emissions (actual) per Facility Square Foot 23.19 pounds
<br />Level of Confidence:High1
<br />Weather Normalized Totals***
<br />Normalization Factors
<br />HDD Normalizaiton Factor 112.68%
<br />CDD Normalization Factor 92.55%
<br />Normalized Energy Use
<br />Weather Normalized Total Electrical Use 3,156,010.26
<br />Weather Normalized Total Gas Use 149,186.77
<br />Normalized GHG Emissions
<br />Weather Normalized Electrical GHG 2,461.69 Metric Tonnes
<br />Weather Normalized Gas GHG 790.99 Metric Tonnes
<br />Total GHG Emissions (Normalized)3,252.68 Metric Tonns
<br />Level of Confidence:High1
<br />* Electicity factor based on supplier provided data, reported in Regional Indicators Initiative
<br />****Waste Water Treatment Plant energy use included in Water and Waste Water section
<br />** Natural Gas factor based on EPA data https://www.epa.gov/energy/ghg-equivalencies-calculator-
<br />calculations-and-references
<br />*** Weather Normalized totals adjust energy use and GHG levels based on adjustments of Year against the
<br />region's 30 year average as determined through Heating (HDD) and Cooling Degree Days (CDD) for year as
<br />reported by NOAA http://www.ncdc.noaa.gov/climate-information. Factor is applied to 80% natural gas
<br />consumption and to 25% electricity consumption (typical heating and air conditioning shares)
<br />1 High confidence level based on high quality energy metering and tracking at all facilities, emission factor rates
<br />from utility companies, EPA and DOE coincide, and normalization HDD and CDD calculations based on NOAA
<br />records.
|