Laserfiche WebLink
exceed 25 kW spaced at least 15 seconds apart. <br /> Manual Disconnect. A means shall be available to manually disconnect or <br /> shut down all or a portion of the Customer's load when requested to do so by <br /> ERMU or its designated agent. Manual reconnect to the utility source shall be <br /> made in increments not to exceed 25 kW spaced at least 15 seconds apart. <br /> Section 3: Power Quality. Operation of Customer's load disconnect equipment <br /> must not cause any reduction in the quality of service provided by ERMU to its other <br /> customers nor interfere with the operation of the Distribution System or ERMU's <br /> power supplier's transmission system. If, in the opinion of ERMU, quality of service <br /> to other customers is compromised, it shall be the responsibility of Customer to take <br /> any corrective action that may be required and/or for reimbursing ERMU for the cost <br /> of corrective action which ERMU deems necessary to provide and restore service to <br /> prescribed limits. Operation of Customer's load disconnect equipment shall be made <br /> in a manner such that Total Harmonic Distortion (THD) levels shall be less than 1% <br /> and power factor of 95% lagging or higher is maintained. <br /> ARTICLE 5. LOAD DISCONNECT or INTERRUPTION OPERATION Upon not <br /> less than thirty minutes notice by ERMU or its designated agent, Customer shall interrupt <br /> enough load to attain the PDL as stated in Article 1. During such period ERMU shall not be <br /> obligated to serve that portion of the load interrupted to reach the PDL. Exceptions to the <br /> thirty minute notice may occur in system emergency situations, but every attempt will be <br /> made to give as much advance notice as possible under system emergency situations. <br /> ARTICLE 6. COMPENSATION TO CUSTOMER. <br /> Section 1: ERMU shall compensate Customer for load interruptions maintained at <br /> or below the PDL when requested by ERMU or its designated agent, at the rates <br /> indicated below: <br /> Monthly Credit/Kw* <br /> Summer (June, July, and Aug) $14.00 per kW <br /> Winter (Dec, Jan, and Feb) $10.00 per kW <br /> Spring/Fall (Mar,Apr, May, Sept, Oct,Nov $ 6.00 per kW <br /> *Credit applies only during months in which Customer coincidental peak <br /> demand is at least 100 kW over the PDL. <br /> The difference between Customer's coincidental peak demand at the time of notice to <br /> interrupt and the PDL shall be used as a basis for establishing Customer's monthly <br /> credit. In months in which no notice to interrupt is given, the difference between <br /> Customer's coincidental peak demand and the PDL shall be used as a basis for <br /> establishing Customer's monthly demand credit. <br /> In the event that participating customers are not controlled during the Coincidental Peak <br /> Demand hour, the customer will receive applicable demand credits only for metered Demand <br /> 3 <br /> 92 <br />