We began water testing above locker room 7 by <br />spraying water onto the roof termination at the <br />wall. No leakage occurred after 20 minutes of <br />spraying. <br /> <br />1 Z ~ ~ '~ ~ J <br />AR <br />~~,. <br />is <br />i.. <br />~tt~I~~ <br />~ ~~ <br />,. <br />i. <br />We then proceeded to spray the wall using a <br />spray bar to simulate rain fall. One of the spray <br />nozzles focused on a vertical crack in the wall. <br />Leakage occurred at the head of the door going <br />into Locker Room 7 within 5 minutes of <br />spraying. We opened the ceiling access panel <br />and could see water coming out of a vertical <br />crack located above the door. <br />21 <br />